Trouble Shooting
PowerLine Connectivity
If the connectivity fails please check the following
-
Is the ethernet cable plugged in to the MPI adapter on
X122
orX101
-
Check the MPI settings (address), PLC Rack and PLC Slot numbers.
- If you use the interface
X122
, usenck-mpi=3
,plc-slot=2
,plc-rack=0
- If you use the interface
X101
, usenck-mpi=13
,plc-slot=13
,plc-rack=0
NOTESome machine builder reconfigure these standard settings from Siemens.
- If you use the interface
-
Check if there are free MPI resources available. The number of participants are limited.
-
Check the settings on the MPI-to-Ethernet adapter. The following example shows the configuration of the
S7-LAN
adapter.-
Ensure the local device address is free (like 20 in this example).
-
Scan the the bus and check where the NCU is configured In the following example, on
nck-mpi=3
. Note that the other device might be the PLC.
-
-
Check the settings on the Sinumerik HMI, if communication is enabled on the interface.