Skip to main content
Version: 2.6

Modbus TCP Control Driver Configuration

Plugin Configuration

The plugin configuration file is named settings.json located in <install directory>\Config\HumanOS.UHAL.ModbusTcpControl\. It contains all global settings of the plugin.

See Generic Plugin Configuration for more details.

The plugin is a polling-based plugin. The performance depends on the following factors:

  • Location of the HumanOS® Runtime Host (from a network view, place as near as possible to the PLC)
  • Number of TCP connections available for the Driver to the device

Plugin Configuration Extension

The FANUC Plugin extends the Generic Plugin Configuration with

  • Sub Task processing
  • Task Processor Memory Assignment
  • Alarm and Event Settings

Figure 1: Configuration model of the Modbus TCP Plugin

Extension: Sub Task Processor

The configuration contains one or more task processors (threads) that handle different facets of the MODBUS control driver, like:

  • Memory management (command, read, write and monitoring)
  • Alarm and event management

At least one processor is needed. It is called MainTaskProcessor.

Additionally, different sub task processors can be added named SubTaskProcessor. They allow to manage specific facets of the driver in parallel. Several tasks can be predefined and added to the processors.

Extension: Task Processor Memory Assignment

By default, all memory types are mapped to the main task processor. The memory mapping helps to assign the memory type address to another task processor. This helps to distribute the data processing load to different tasks (threads).

Note that if two task processors use the same memory mapping, the workload is split among these processors.

AttributeDescriptionData Type
MemoryTypeMemory type of the assigned memory. This setting is optional. If empty, all memory types of the memory base are handled by this processor.EMemoryType

Following example assigns the "Alarming" MemoryType to the SubTaskProcessor "Alarming":^

{
"Name": "AlarmEventProcessor",
"ProcessingPriority": "Normal",
"MaxSchedulingTimeSlice": 500,
"MinSchedulingTimeSlice": 100,
"MemoryMappings": [
{
"MemoryType": "Alarming"
}
]
}
CAUTION

Use the processing priority setting carefully!! Impropriate settings may cause high processor loads and could slow down the overall system performance. We recommend that only one of the processors is set to “Highest”.

Extension: Alarm and Event Handling

It is recommended to use a separate task processor for alarming and OEM message mapping.

For alarm reading, see Alarm Address.

Example

Following example shows a configuration of two task processors. The "MainTaskProcessor" handles the commanding, reading, writing and monitoring or all memories within the device. The "AlarmEventProcessor" manages the alarm and events.

{
"Disabled": false,
"Devices": [
{
"MainTaskProcessor": {
"Name": "Main TaskProcessor",
"ProcessingPriority": "Highest",
"MaxSchedulingTimeSlice": 5,
"MinSchedulingTimeSlice": 1
},
"SubTaskProcessors": [
{
"Name": "AlarmEventProcessor",
"ProcessingPriority": "Normal",
"MemoryMappings": [
{
"MemoryType": "Alarming"
}
]
}
]
}
]
}

Device Information File

The device information file is used to configure the access devices by MODBUS protocol. It contains:

  • Id: unique device id (GUID), which MUST match the device license id.
  • DriverId: 4a06a655-36c2-4430-ae27-aaaa4a431395
  • Address: Connection address
  • Data Access
  • Alarm Events

See Device Information Model for more details.

Connection Address for Modbus TCP

The Address for Modbus TCP connections must be provided like following:

NameDescriptionExample
AddressIP addressaddress=10.256.35.32
PortTcp Portport=502
SlaveIdModbus Slave IDslaveid=1

All three parameters are used as the address string, separated by semicolons.
Example: address=10.256.35.32;port=502;slaveid=1

Connection Address for Modbus RTU

INFORMATION

If the RTU connection is to be used, the Property "ConnectionType" must be set in the device root node.
It's value must be "Rtu".

The Address for Modbus RTU connections must be provided like following:

NameDescriptionExample
AddressCOM Addressaddress=COM3
SlaveIdModbus Slave IDslaveid=1

For Windows machines, the COM resource is specified as the address.
Example: COM3
For Linux machines, the address is the path to the COM interface.
Example: /dev/ttyRS485

Both parameters are used for the address string, separated by a semicolon.
Example: address=/dev/ttyRS485;slaveid=1

The following additional connection properties can be set in the device model as property of the device root node:

NameDescriptionData TypePossible ValuesDefault Value
RtuTimeoutTimeout for the Rtu connection in millisecondsSystem.Int3250
BaudRateConnection baud rateSystem.Int32115200
DataBitsNumber of data bitsSystem.Int325, 6, 7, 88
StopBitsNumber of stop bitsSystem.String0, 1, 1.5, 21
ParitySerial port paritySystem.Stringnone, even, mark, odd, spacenone

Property MemorySizes

To ensure a correct functioning, each Element which is accessed on the device (e.g. Register, Input, Output, etc...) must be declared with its maximum accessible size. Since the driver always fetches more than the declared data, it is crucial to set its register limits. This will then be added to the Device Properties. The default block size fetched is 120 + 3 (256 bytes) for 16-bit registers and 1992 + 8 for 1-bit registers (250 bytes).

Example for OpenPLC:

{
"Name": "MemorySizes",
"Value": "InputBit:*=799\nCoilBit:*=799\nInputRegister:*=1023\nHoldingRegister:*=8191"
}

Property PageSizes

Not all devices support transfers of 256 bytes at once. If the device only supports 64 bytes, then the below example fits the need:

Example for Device:

{
"Name": "PageSizes",
"Value": "InputBit=248\nCoilBit=248\nInputRegister=29\nHoldingRegister=29"
}

In the example above, the settings are in bits for InputBit and CoilBit, and in words for InputRegister and HoldingRegister. Insert this as Device Property, if nothing is declared the values listed in chapter Property MemorySizes are used.

Modbus TCP Memory Locations and Sizes

CAUTION

This data is device specific. The example shown below is valid for OpenPLC!

As mentioned, these offsets and data sizes are device dependent. For example, on an OpenPLC looks like this:

Memory TypeRangeExampleModbus memory offset
InputBitI0.0 – I99.7InputBit.Boolean:1.0 = I1.00
CoilBitQ0.0 – Q99.7CoilBit.Boolean:2.2 = Q2.20
InputRegisterIW0 - IW1023InputRegister.UInt16:10 = IW100
HoldingRegisterMW1024 - MW2047 / DW2048- DW4095 / LW4096 - LW8191HoldingRegister. UInt16:1024 = MW0; HoldingRegister. UInt8:1025 = MW1; HoldingRegister.Float32:2048 = DW1; HoldingRegister. UInt32:2050 = DW2; HoldingRegister.Float64:2048 = LW1; HoldingRegister. UInt64:2052 = LW21024(16-bit) /2048(32-bit) /4096(64-bit)

As seen the value which is stored in the holding registers or input registers is always 16 bits long, despite the data type.

Registers explained

As seen in the chapters before, modbus has different registers. From a data type view, there are only two different registers: a bitwise and a 16-bit register.

The InputBitRegister and CoilBitRegister can only be addressed bitwise.

The InputRegister and HoldingRegister are 16-bit registers, which means they can hold all data types supported. For data types bigger than 16-bit like double words (UInt32), two or more registers must be combined.

In newer modbus devices, these ranges are declared (see image in previous chapter).

If a double word value is needed the definition on the different platforms looks like this (openplc example):

Definition programming software plc: %DW0

Definition HumanOS® Address: Holdingregister.UInt32:2048

The next address would look like this:

Definition programming software plc: %DW1

Definition HumanOS® Address: Holdingregister.UInt32:2050

Keep in mind that the counting of the HumanOS® address is dependent on the absolute offset of the modbus device, so as shown, if two combined registers are used, the offset is raised by 2, for 64-bit combined values by 4.

For values lower than 16-bit e.g. byte (UInt8) the used memory space is still 16-bit, the offset is raised by one.

Calculating the maximum Memory Size

If the maximum memory size of the target is unknown or it is not necessary to fetch that much data, the maximum memory size per target can be calculated like following:

Search for the address with the highest offset per target. Calculate the maximum target range with help of the data type.

Example Address: HoldingRegister.Float32:14

Example

{
"Id": "7ea0317f-8f83-4e3e-a822-7498de01240f",
"Name": "OpenPLC",
"DriverId": "4a06a655-36c2-4430-ae27-aaaa4a431395",
"Address": "address=10.196.24.11;port=502;slaveId=1",
"Properties": [
{
"Name": "MemorySizes",
"Value": "InputBit:*=799\nCoilBit:*=799\nInputRegister:*=1023\nHoldingRegister:*=8191"
}
],
"DataNodes": [
{
"Id": "e7c89c04-ff87-4951-95fa-6be81a29442d",
"Name": "input00",
"DataClass": "Event",
"DataType": "System.Boolean",
"Address": "InputBit.Boolean:0.0",
"Access": {
"Read": true,
"Receive": true
},
"HistoryMode": {
"Retention": 100,
"SamplingRate": 2000
}
},
{
"Id": "14AE9CB7-6155-46EB-9A8D-8C859A75E7C8",
"Name": "output00",
"DataClass": "Event",
"DataType": "System.Boolean",
"Address": "CoilBit.Boolean:0.0",
"Access": {
"Read": true,
"Receive": true
},
"HistoryMode": {
"Retention": 100,
"SamplingRate": 2000
}
},
{
"Id": "99CBDAB9-D5DC-470A-85F4-71EBB177C0AF",
"Name": "inputreg",
"DataClass": "Event",
"DataType": "System.UInt16",
"Address": "InputRegister.UInt16:0",
"Access": {
"Read": true,
"Receive": true
},
"HistoryMode": {
"Retention": 100,
"SamplingRate": 2000
}
},
{
"Id": "04E7DEDE-2D32-4CD7-9573-FF895BF7E550",
"Name": "qw1",
"DataClass": "Event",
"DataType": "System.UInt32",
"Address": "HoldingRegister.UInt32:1",
"Access": {
"Read": true,
"Receive": true
},
"HistoryMode": {
"Retention": 100,
"SamplingRate": 2000
}
}
]
}